Section 903.2 of the IFC is amended to read as follows:

903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in this section.

* * *

903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area.

Exception: Group R-3 occupancies subject to the requirements of the International Residential Code.

903.2.8.3 Application to existing structures. Automatic sprinklers shall be installed, tested and approved:

1. Whenever an existing building containing a Group R fire area is being substantially remodeled or renovated.

2. Whenever an existing building containing a Group R fire area incurs fire damage requiring repairs meeting the definition of substantial remodel/renovation.

3. In all existing hotels and motels annexed into the City of Gig Harbor within five years of the effective date of the annexation.

* * *

(Ord. 1263 § 5, 2013; Ord. 1186 § 7(L), 2010; Ord. 983 § 16, 2005).